SEKO Tekba & Komba Metering Pump: Parameter Setup & Fault Light Guide
Italian SEKO metering pumps (Tekba and Komba digital solenoid series) are widely used in cooling towers, RO skids, and municipal water treatment. Engineers often look up how to configure sub-series parameters and diagnose fault LEDs. Using official specs from our SEKO Tekba and SEKO Komba pages, this guide covers both.
1. Tekba vs. Komba Series Overview
- SEKO Tekba Series:
2.5–110 L/h, max20 bar, coveringEMS / EML / EMC / EMM / EMGcontrol options. - SEKO Komba Series: Compact
1–9 L/h, max10 bar, coveringDMS / DML / DMC / DMMoptions.
2. Parameter Setup by Control Mode
Manual Frequency (EMS / DMS)
Use the front keypad to adjust stroke frequency (0%–100%) directly for constant dosing.
Analog 4–20 mA Mode (EMM / DMM)
Enter the setup menu, select mA mode, and map 4.0 mA to 0% and 20.0 mA to 100% (or invert for alkaline/acid reverse proportional dosing).
Pulse Water-Meter Mode (EMC / DMC)
Configure 1:N multiplication or N:1 division ratios against water-meter pulses for flow-paced dosing.
3. Why Does the SEKO Fault Light Turn On?
- Low-Level Tank Interlock: Float switch opened on an empty tank.
- Coil Over-Temperature / Overload: Running continuously near
20 barin high ambient heat. - 4–20 mA Loop Loss: Input current dropped below
3.5 mA. - Remote Standby: External dry-contact stop signal active (slow blink, not a hardware fault).
Conclusion
Matching SEKO sub-series codes (S/L/C/M/G) to your control loop simplifies setup and speeds up fault diagnosis. For manuals or spare diaphragms, contact our team.
FAQ
What do EMS, EMC, and EMM mean on SEKO pumps?
S = manual frequency, L = low-level input, C = pulse proportional, M = 4–20 mA analog, and G = multi-function.
Why are the keypad buttons unresponsive?
Check whether Key Lock is active (hold the unlock combo for 3 seconds) or if the pump is in external remote mode.
Are Tekba and Komba diaphragms interchangeable?
No, they use different head sizes and bolt patterns—always order by exact nameplate code.
Can SEKO pumps link directly to a pH transmitter?
Yes, EMM and DMM models accept direct 4–20 mA input from pH/ORP controllers.
What should I do if the red fault LED stays on with no clicking?
Disconnect external level/remote plugs to test standalone; if the fault persists, inspect supply voltage and the driver board.