Zhejiang Weilan Technology Co., Ltd.

Do Metering Pumps Auto-Restart After a Power Outage? Electrical Interlock Rules

Author: Zhejiang Weilan Technology Co., Ltd.Source: Official sitePublished: Category: News
Summary: Comparing EEPROM auto-resume on digital solenoid pumps vs contactor latching on mechanical pumps, plus mandatory main-pump interlocks for unattended stations.

When plant power flickers off for 5 seconds at midnight and returns, what happens in an unattended chemical room? If a disinfection pump fails to restart, treated water goes off-spec; if an acid pump restarts while the main water pump stays off, concentrated acid pools inside a stagnant pipe.

1. Solenoid vs Mechanical Pump Behavior

  • Digital Solenoid Pumps (EEPROM Memory): Models like Tekna, AX1, and DFD/EvoDose remember their pre-outage run/stop state and auto-resume dosing on power restoration if they were running before the outage.
  • Three-Phase Mechanical Pumps: With a traditional momentary push-button latched contactor, the pump stays OFF after power returns until an operator presses Start; with a maintained 2-position selector switch or PLC run output, it auto-restarts.

2. Two Mandatory Unattended Interlocks

  1. Hardwire Main Feed Pump Auxiliary Contact: Cut dosing control power whenever the main water pump is off.
  2. Use Standby Dry-Contact Input for Frequent Cycling: Never cycle mains 220V power repeatedly on microprocessor solenoid pumps; use the dedicated Standby/Enable low-voltage input.

Conclusion

Combine maintained/EEPROM auto-resume with hardwired main-pump and low-level interlocks for safe unattended recovery. See Products or Contact Us.

FAQ

Why did chemical siphon back into the tank during a power outage?

Missing or failed discharge backpressure/check valves allowed pressurized header water to flow backward through the pump head.

Can a push-button mechanical pump panel be converted for safe auto-restart?

Yes—replace the momentary start/stop buttons with a maintained Auto/Off/Hand selector switch wired in series with the main water pump auxiliary contact.

Get a Quote

Leave your requirements and we will reply within 1 business day

Inquire Now →