Installing a backpressure valve and a safety relief valve in the wrong order on a chemical dosing discharge line is one of the fastest ways to crack a pump head or lose siphon protection.

1. The Mandatory Piping Sequence

Along the discharge flow direction, components must follow this exact sequence: Pump Discharge -> Pulsation Dampener -> Safety Relief Valve -> Pressure Gauge -> Backpressure Valve -> Injection Point.

Why must the safety relief valve sit upstream of the backpressure valve? If the backpressure valve clogs with dried chemical or a downstream isolation valve is accidentally closed, pressure builds immediately after the pump head. Placing the relief valve upstream ensures overpressure is vented safely back to the tank top before the pump head ruptures.

2. Standard Pressure Setpoints

  • Backpressure Valve: Typically set between 1.5 and 3.0 bar (0.15–0.30 MPa), or at least 1.0 bar above the maximum positive suction head, to prevent gravity siphoning and ensure crisp check-valve ball seating.
  • Safety Relief Valve: Typically set 10%–25% above normal system operating pressure (for example, 7.5–8.0 bar on a 10 bar rated pump operating at 5 bar), while staying below the weakest pipe rating.
  • Relief Return Line: Route the relief discharge independently back to the top of the chemical tank above the liquid level so no backpressure acts on the relief outlet.

Conclusion

Keep the relief valve closest to the pump head, place the backpressure valve downstream, and route the relief return above the tank liquid level. Visit our Products or Contact Us for pre-tested UPVC, PVDF, and SS316L valve assemblies.

FAQ

Do I need a backpressure valve if line pressure is already 5 bar?

If downstream pressure remains continuously above 3 bar under all operating and shutdown conditions, a separate backpressure valve may not be required; otherwise, install one at 1.5–2.0 bar to prevent siphoning during line drainage.

Can I use a manual ball valve instead of a backpressure valve?

No. A manual valve only creates variable throttling and cannot maintain constant backpressure or prevent siphoning when flow stops.